1 Owners Installation, Operation, and Safety Manual 3200 Series DC High Flow Fuel Transfer Pump Models FR3210B, FR3204 Tuthill Transfer Systems 8825
10 Operating Instructions 1. If so equipped, reset Meter to “0” (do not reset while in use as this can cause damage to the meter). 2. Remove dispens
11 Trouble Shooting The following Trouble Shooting guide is provided to offer basic diagnostic assistance in the event you encounter abnormal service
12 Trouble Shooting (cont’d) Motor stalls / Fuse blows or circuit breaker trips repeatedly. 1. Bypass valve sticking. Remove and inspect valve; must m
13 Motor Power -AC 115, 230, 115/230 N/A HZ 50, 60, 50/60 N/A Power - DC 12, 24, 12/24 12 VOLT HP (horsepower) rating 1/2 HP Power c
14 Kit Number Description KIT320RK Overhaul Kit KIT320RG Rotor & Vane Kit KIT320SL Seal Kit KIT320BV By-Pass Service Kit Parts Rotor, rotor c
15 Safety Testing Approvals The Fill-Rite line of pumps have been safety tested for compliance to the standards set forth by Underwriters Laboratorie
16 DC000834-000 Rev 0 Visit us on the web at: www.fillrite.com Learn more about Tuthill Corporation and our family of high quality, value minded produ
2 Table of Contents Table of Contents ...
3 Safety Information WARNING! Electrical wiring should be performed ONLY by a licensed electrician in compliance with local, state, and national elec
4 CAUTION! A pressure retaining fill cap can be used to reduce fuel loss through evaporation, but note that it will reduce the flow rate. Typical S
5 1. Thread the 1-1/4” pipe into the tank adapter. Seal threads liquid tight with appropriate sealant. (Figure 1) Materials: • 1-1/4” pi
6 Electrical Wiring Wiring Procedure 2. Screw the inlet flange (with suction pipe) into the tank flange; seal threads liquid tight with appropria
7 1. Remove pump’s electrical junction box cover and straighten the 2 wires to make the stripped wire ends accessible outside of the junction box. 2.
8 DC Wiring (cont’d) Figure 4 Wire in Junction Box For Skid Mounted Tanks 1. Pass the electrical wires to the power source, supporting the wires as
9 Wiring Diagram 50 amp fuse located outside of hazardous area. See installation guidelines for size. 50 amp fuse located outside of hazardous area.